• Copper Rope

    Copper Rope

    • Conductor:

      Bare Copper Conductor of Class 1/2/5/6 (Solid)

    • Copper Content:

      99.97% Pure Copper

    • Insulation:

      None

    • Description
    • Technical Data
    • Application
    • Packing & Delivery
    Description Copper Rope
    Conductor: Bare Copper Conductor of Class 1/2/5/6 (Solid)
    Copper Content 99.97% Pure Copper
    Insulation: None
    Cores x conductor cross-section Calculated cross-sections Construction External diameter Permitted stress Conductor resistance at 20 °C Rope weight
        nominal approx. max. max. nominal
    mm² mm² n x mm mm kN Ω/km kg/km
    10 10,02 7x1,35 4,1 4,02 18,072 90
    16 15,89 7x1,70 5,1 6,37 11,385 142
    25 24,25 7x2,10 6,3 09,72 0,7460 217
    35 34,36 7x2,50 7,5 13,77 0,5265 308
    50 49,48 7x3,00 9,0 19,84 0,3656 443
    50 48,35 19x1,80 9,0 19,38 0,3759 433
    70 65,81 19x2,10 10,5 26,38 0,2762 590
    95 93,27 19x2,50 12,5 37,39 0,1949 836
    95 93,11 37x1,79 12,5 37,39 0,1949 834
    120 116,99 19x2,80 14,0 46,90 0,1554 1048
    120 117,40 37x2,01 14,1 46,90 0,1554 1052
    150 147,11 37x2,25 15,8 58,98 0,1238 1318
    185 181,52 37x2,50 17,5 72,81 0,1003 1627
    240 242,54 61x2,25 20,3 97,23 0,0753 2173
    300 299,43 61x2,50 22,5 120,04 0,0610 2683
    400 400,14 61x2,89 26,0 160,42 0,0456 3585
    500 499,83 61x3,23 29,1 200,38 0,0365 4479
    Used as earth connection, for flexible lines and connection, in distribution networks for connecting of metal parts, and for overhead electric lines.


     